Volvo Penta generator series
250 - 760 kVA

on skid frame or soundproofed

Volvo power generators 250 – 760 kVA – 1.500 r.p.m diesel watercooled

85 to 760 kVA Volvo power generator
Volvo generator type kVA 100 %
PRP*
Engine type
WA-V 85 85 TAD 530 GE
WA-V 100 100 TAD 531 GE
WA-V 130 130 TAD 532 GE
WA-V 150 150 TAD 731 GE
WA-V 180 180 TAD 732 GE
WA-V 200 200 TAD 733 GE
WA-V 250 250 TAD 734 GE
WA-V 300 300 TAD 1341 GE
WA-V 350 350 TAD 1342 GE
WA-V 380 380 TAD 1343 GE
WA-V 400 450 TAD 1344 GE
WA-V 450 454 TAD 1345 GE
WA-V 500 508 TAD 1641 GE
WA-V 600 595 TAD 1642 GE
WA-V 610 610 TWD 1643 GE
WA-V 640 640 TWD 1643 GE
WA-V 660 660 TWD 1644 GE
WA-V 700 700 TWD 1645 GE
WA-V 760 760 TWD 1744 GE

*Prime Power PRP. Maximum power for variable load, no time limit per year. The average 24 hours operation should not exceed 80% of that power. For control purposes and start-up of heavy machinery an overload of 10% is permissible for 1 hour within 12 hours. Operating mode according to ISO 8528. The maintenace is to be considered.

74 to 645 kW Volvo power generator
Volvo generator type Power
KWm.
Consumption
100 % load PRP
WA-V 85 74 KW 19,00 L/h
WA-V 100 88 KW 23,00 L/h
WA-V 130 112 KW 29,00 L/h
WA-V 150 133 KW 34,00 L/h
WA-V 180 160 KW 41,00 L/h
WA-V 200 177 KW 46,00 L/h
WA-V 250 217 KW 52,00 L/h
WA-V 300 275 KW 68,00 L/h
WA-V 350 303 KW 68,00 L/h
WA-V 380 325 KW 82,00 L/h
WA-V 400 354 KW 83,00 L/h
WA-V 450 388 KW 92,00 L/h
WA-V 500 430 KW 102,00 L/h
WA-V 600 503 KW 117,00 L/h
WA-V 610 536 KW 120,00 L/h
WA-V 640 536 KW 120,00 L/h
WA-V 660 555 KW 130,00 L/h
WA-V 700 595 KW 139,00 L/h
WA-V 760 645 KW 154,00 L/h
Data sheets Volvo power generator
Volvo generator type Datasheet
WA-V 85 PDF
WA-V 100 PDF
WA-V 130 PDF
WA-V 150 PDF
WA-V 180 PDF
WA-V 200 PDF
WA-V 250 PDF
WA-V 300 PDF
WA-V 350 PDF
WA-V 380 PDF
WA-V 400 PDF
WA-V 450 PDF
WA-V 500 PDF
WA-  600 PDF
WA-V 620 PDF
WA-V 640 PDF
WA-V 660 auf Anfrage
WA-V 700 auf Anfrage
WA-V 760 auf Anfrage

Volvo generators, model “G” on base frame

Version “G”: Stationary version (open design) on base frame

Tank capacity and length Volvo power generator
Volvo generator type Tank capacity
in L
Length
in mm
WA-V 85 „G“ 180 2.050
WA-V 100 „G“ 180 2.080
WA-V 130 „G“ 212 2.360
WA-V 150 „G“ 236 2.500
WA-V 180 „G“ 236 2.500
WA-V 200 „G“ 236 2.500
WA-V 250 „G“ 470 3.000
WA-V 300 „G“ 470 3.000
WA-V 350 „G“ 470 3.000
WA-V 380 „G“ 470 3.000
WA-V 400 „G“ 470 3.000
WA-V 450 „G“ 470 3.000
WA-V 500 „G“ 580 3.490
WA-V 600 „G“ 580 3.490
WA-V 610 „G“ 990 3.500
WA-V 640 „G“ 990 3.500
WA-V 660 „G“
990 3.500
WA-V 700 „G“ 990 3.620
WA-V 760 „G“ 990 3.620
Width and height Volvo power generator
Volvo generator type Width
in mm
Height
in mm
WA-V 85 „G“ 930 1.713
WA-V 100 „G“ 930 1.719
WA-V 130 „G“ 1.035 1.763
WA-V 150 „G“ 1.035 1.737
WA-V 180 „G“ 1.035 1.737
WA-V 200 „G“ 1.035 1.737
WA-V 250 „G“ 1.200 1.834
WA-V 300 „G“ 1.200 2.160
WA-V 350 „G“ 1.200 2.163
WA-V 380 „G“ 1.200 2.141
WA-V 400 „G“ 1.200 2.141
WA-V 450 „G“ 1.200 2.111
WA-V 500 „G“ 1.300 2.226
WA-V 600 „G“ 1.300 2.219
WA-V 610 „G“ 1.330 2.400
WA-V 640 „G“ 1.330 2.400
WA-V 660 „G“ 1.330 2.816
WA-V 700″G“ 1.330 2.816
WA-V 760″G“ 1.330 2.816
Weight Volvo power generator
Volvo generator type Weight
in KG
WA-V 85 „G“ 1.240
WA-V 100 „G“ 1.300
WA-V 130 „G“ 1.480
WA-V 150 „G“ 1.580
WA-V 180 „G“ 1.850
WA-V 200 „G“ 1.820
WA-V 250 „G“ 2.050
WA-V 300 „G“ 2.800
WA-V 350 „G“ 2.850
WA-V 380 „G“ 2.940
WA-V 400 „G“ 2.940
WA-V 450 „G“ 3.180
WA-V 500 „G“ 3.620
WA-V 600 „G“ 3.680
WA-V 610 „G“ 4.330
WA-V 640 „G“ 4.350
WA-V 660 „G“ 4.500
WA-V 700 „G“ 4.750
WA-V 760 „G“ 4.850

“S” Silenced Volvo diesel gensets

Version “S”: with weatherproof sound insulation hood

Tank capacity and db (A) Volvo power generator
Volvo generator type Tank capacity
in L
db(A)*
7 Meter
WA-V 85 „S“ 220 72
WA-V 100 „S“ 220 70
WA-V 130 „S“ 220 70
WA-V 150 „S“ 220 72
WA-V 180 „S“ 360 70
WA-V 200 „S“ 360 70
WA-V 250 „S“ 360 72
WA-V 300 „S“ 534 72
WA-V 350 „S“ 534 72
WA-V 380 „S“ 534 72
WA-V 400 „S“ 534 72
WA-V 450 „S“ 534 72
WA-V 500 „S“ 990 75
WA-V 600 „S“ 990 76
WA-V 610 „S“ 990 77
WA-V 640 „S“ 990 77
WA-V 660 „S“ 990 78
WA-V 700 „S“ 990 78
WA-V 760 „S“ 990 81
Length and width Volvo power generator
Volvo generator type Length
in mm
Width
in mm
WA-V 85 „S“ 2.950 1.100
WA-V 100 „S“ 2.950 1.100
WA-V 130 „S“ 2.950 1.100
WA-V 150 „S“ 2.950 1.100
WA-V 180 „S“ 3.600 1.350
WA-V 200 „S“ 3.600 1.350
WA-V 250 „S“ 3.600 1.350
WA-V 300 „S“ 4.200 1.600
WA-V 350 „S“ 4.200 1.600
WA-V 380 „S“ 4.200 1.600
WA-V 400 „S“ 4.200 1.600
WA-V 450 „S“ 4.200 1.600
WA-V 500 „S“ 4.860 2.060
WA-V 600 „S“ 4.860 2.060
WA-V 610 „S“ 4.860 2.060
WA-V 640 „S“ 4.860 2.060
WA-V 660 „S“ 4.860 2.060
WA-V 700 „S“ 4.860 2.060
WA-V 760 „S“ 4.860 2.060
Height and weight Volvo power generator
Volvo generator type Height
in mm
Weight
in KG
WA-V 85 „S“ 1.760 1.680
WA-V 100 „S“ 1.760 1.840
WA-V 130 „S“ 1.763 1.980
WA-V 150 „S“ 1.760 2.180
WA-V 180 „S“ 2.040 2.850
WA-V 200 „S“ 2.040 2.980
WA-V 250 „S“ 2.040 3.018
WA-V 300 „S“ 2.245 4.200
WA-V 350 „S“ 2.245 4.320
WA-V 380 „S“ 2.245 4.600
WA-V 400 „S“ 2.145 4.660
WA-V 450 „S“ 2.245 4.660
WA-V 500 „S“ 2.585 5.940
WA-V 600 „S“ 2.585 6.260
WA-V 610 „S“ 2.585 6.480
WA-V 640 „S“ 2.585 6.660
WA-V 660 „S“ 2.595 6.800
WA-V 700 „S“ 2.595 7.100
WA-V 760 „S“ 2.595 7.500

All specified data “Volvo generator” included in standard delivery.

High performance, maximum availability and fast installation

As Volvo Penta has over 100 years of industrial experience and therefore manufactures high-quality products, it is one of the world’s best-known diesel engine manufacturers. An emergency genset with a Volvo Penta engine is particularly resilient and can start quickly. Thanks to a low oil quantity, high quality and reliability as well as simple installation, the highly efficient engines ensure low operating costs. Maintenance intervals can be limited to up to 1000 hours. Volvo Penta engines are extremely economical and flexible. They meet all the requirements of G3 according to ISO8528-5.

Basic equipment Volvo power generators

Power generator

The complete generating set is mounted on a base frame made of welded steel edge profiles in a robust construction. Specially designed devices for lifting with a crane are attached to the base frame. The diesel engine and the generator are directly connected to each other via an SAE flange, so that there is no possibility of misalignment even after prolonged operation. The day tank is integrated in the base frame. The 12 / 24 volt DC starter batteries are mounted on the base frame and wired to the diesel engine.

Engine

Volvo industrial diesel engine 4-stroke direct injection, water-cooled 1,500 rpm (50 Hz). Low oil-fuel consumption with long maintenance intervals makes series a very economical engine application.

Generator

Mecc Alte, Stamford or Leroy Somer three-phase synchronous generator, brushless, self-regulating with electronic voltage regulator (AVR) to VDE 0100 Part 0530, 400/230 volts, 4-pole, insulation to Class H.

Switchgear

Manual start/stop system mounted on the generator set with engine monitoring and shutdown in the event of low oil pressure, overtemperature, overspeed, 3-pole generator switch with thermal and magnetic release. Optionally with fully automatic emergency power switchgear

Equipment

Frequency meter, operating hours counter, voltmeter and ammeter, visual and acoustic alarm display in the event of a malfunction of the generator set.

Documentation

Complete description, clearly filed for the engine, alternator and the entire system.

Work test

Every generator is tested in the test bay before leaving the factory.

Quality standards

WA Notstromtechnik GmbH backup power generators comply with the CE mark and the following additional regulations:

  • 2006/42/ EC | CE & EN ISO 13857: 2008 Machine safety.
  • ISO 8528-5: 2018-10 Power generating sets with reciprocating internal combustion engines Part 5
  • 2014/30/EU Electromagnetic compatibility.
  • 2006/95/EC Low Voltage Directive
  • 2014/35/EU Electrical equipment designed for use within certain voltage limits
  • 2000/14/CE Exposure of machinery to noise Outdoor use. (modified by 2005/88/CE)
  • 2002/88/CE Exhaust emissions and particulate emissions. (modified by 2004/26/CE)
  • AwSV Requirements for systems for handling substances hazardous to water & WHG (valid since 01.08.2017)
  • EN 12100, EN 60204

Performance and installation conditions standardized according to DIN 6271 and ISO 3046: 1000 mbar, 25ºC, 30% relative humidity. If your application is part of a legally required safety power supply, for example for the operation of a sprinkler system, special requirements may be placed on the backup power unit and its peripherals. The team at WA Notstromtechnik GmbH will be happy to advise you on this and accompany your project through to final commissioning.

Optional at extra cost

backup power supplies are available in accordance with the following regulations:

  • DIN VDE 0100 – 551 (2018-12) Installation of low-voltage systems, other equipment
  • DIN VDE 0100 – 560 (2022-10) Installation of low-voltage systems, safety power sources
  • DIN VDE 0100 – 710 (2012-10) Installation of low-voltage systems, areas used for medical purposes
  • DIN VDE 0100 – 718 (2014-06) Requirements for premises and installations of a special kind, Public facilities
  • DIN 6280 – 13 (1994-12) Safety power supply in hospitals and buildings for gatherings of people
  • DIN EN ISO 8528 – 13 (2017-03) Generating sets with reciprocating internal combustion engines Part 13 Safety
  • VdS CEA 4001 (2024-01) Requirements for generating sets for sprinkler systems
  • DIN VDE AR – N 4105 (2018-1) Generating sets on the low-voltage grid
  • 2016/1628 Exhaust gas emissions and pollutant particles (STAGE V)
Warranty

12 months or 2000 operating hours, whichever comes first, up to a maximum of 15 months after notification of readiness for dispatch. If maintenance is not carried out by a specialist company and the monthly test runs are not complied with, the guarantee/warranty claim expires.

 

Technical changes

We expressly reserve the right to make changes.

We are pleased to answer your questions


    I have read and understood the privacy policy. I agree that my details and data will be collected and stored electronically for the purpose of responding to my enquiry. Please note: You can revoke your consent at any time by sending an email to info@wa-strom.com.