MAN emergency power system
250 - 670 kVA

on skid frame or soundproofed

MAN generators with 1,500 rpm at 50 Hz

250 to 670 kVA MAN power generator
MAN generator type kVA 100 %
PRP*
MAN engine type
WA-MA 250
250 D 0836 LE201
WA-MA 315
315 D 2866 LE 201
WA-MA 400
400 D 2876 LE 201
WA-MA 460
460 D 2848 LE 211
WA-MA 500
500 D 2840 LE 201
WA-MA 560
560 D 2840 LE 211
WA-MA 625
625 D 2842 LE 201
WA-MA 670
670 D 2842 LE 211

*Prime Power PRP. Maximum power for variable load, no time limit per year. The average 24 hours operation should not exceed 80% of that power. For control purposes an thrust harder Maschinery is an overload of 10% for 1 hour within 12 hours permitted. Mode according to ISO 8528. The maintenace is to be considered.

216 to 565 kW MAN power generator
MAN generator type Power
KW
Consumption
100 % load PRP
WA-MA 250
216 KW 197 g/Kw/h
WA-MA 315
270 KW 195 g/KW/h
WA-MA 400
340 KW 209 g/KW/h
WA-MA 460
395 KW 210 g/KW/h
WA-MA 500
429 KW 196 g/KW/h
WA-MA 560
480 KW 205 g/KW/h
WA-MA 625
528 KW 195 g/KW/h
WA-MA 670
565 KW 202 g/KW/h

MAN generators, model “G” on base frame

Version “G”: Stationary version (open design) on base frame

Tank capacity and length MAN power generator
MAN generator type Tank capacity
in L
Length
in mm
WA-MA 250 „G“
450 on demand
WA-MA 315 „G“
450 3.508
WA-MA 400 „G“
600 3.726
WA-MA 460 „G“ 600 3.416
WA-MA 500 „G“ 600 on demand
WA-MA 560 „G“ 740 on demand
WA-MA 625 „G“ 740 on demand
WA-MA 670 „G“ 740 on demand
Width and height MAN power generator
MAN generator type Width
in mm
Height
in mm
WA-MA 250 „G“
on demand on demand
WA-MA 315 „G“
1.320 1.880
WA-MA 400 „G“
1.326 1.900
WA-MA 460 „G“ 1.540 1.925
WA-MA 500 „G“ on demand on demand
WA-MA 560 „G“ on demand on demand
WA-MA 625 „G“ on demand on demand
WA-MA 670 „G“ on demand on demand
Weight MAN power generator
MAN generator type Weight
in KG
WA-MA 250 „G“
on demand
WA-MA 315 „G“
2.310
WA-MA 400 „G“
2.464
WA-MA 460 „G“ 2.695
WA-MA 500 „G“  2.750
WA-MA 560 „G“ 2.958
WA-MA 625 „G“  3.500
WA-MA 670 „G“ 3.750

MAN generators, model “S”, soundproofed

Version “S”: with weatherproof sound insulation hood

Tank capacity and db(A) MAN power generator
MAN generator type Tank capacity
in L
db(A)*
7 Meter
WA-MA 250 „S“ 450 68
WA-MA 315 „S“ 450 68
WA-MA 400 „S“ 600 68
WA-MA 460 „S“ 600 67
WA-MA 500 „S“ 600 68
WA-MA 560 „S“ 740 68
WA-MA 625 „S“ 740 68
WA-MA 670 „S“ 740 68

* db(A) gemessen in 7 Metern als Mittelwert einer Rundummessung an 7 Messpunkten

Width and height of MAN generator set
emergency power system type length
in mm
width
in mm
WA-MA 250 „S“ 6.048 2.480
WA-MA 315 „S“ 6.048 2.480
WA-MA 400 „S“ 6.048 2.480
WA-MA 460 „S“ 6.048 2.480
WA-MA 500 „S“ 6.048 2.480
WA-MA 560 „S“ 6.048 2.480
WA-MA 625 „S“ 6.048 2.480
WA-MA 670 „S“ 6.048 2.480
Weight MAN generator set
emergency power system type height
in mm
weight
in KG
WA-MA 250 „S“ 2.600 7.535
WA-MA 315 „S“ 2.600 7.850
WA-MA 400 „S“ 2.600 8.040
WA-MA 460 „S“ 2.600 8.525
WA-MA 500 „S“ 2.600 9.270
WA-MA 560 „S“ 2.600 9.300
WA-MA 625 „S“ 2.600 9.500
WA-MA 670 „S“ 2.600 9.700

All data in basic model or series delivery

Basic equipment MAN power generator

Power generator
The complete power generator is mounted on a steel base frame. On the steel base frame are specially designed devices, for lifting with a crane or Forklift. The diesel engine and the alternator are connected to a SAE-flange, that even a longer period of operation no possibility of an adjustment exists. The daily fuel tank is integrated in the steel base frame. The starter batteries of 12 or 24 volts are fixed on the steel base frame. reheating-system 230 Volt DC.
Engine
MAN industrial diesel 4-stroke direct injection, watercooled 1.500 rpm (50 Hz). Low oil and fuel Consumption with long maintenance intervals make a very economic engine application.
Alternator
Mecc Alte alternator, brushless self-exciting, self-regulating with electronic voltage regulator (AVR) according to VDE 0530, 400/230 volts, 4-pole, insulation class H.
Control Panel
Manual start-stop-system with engine shutdown during monitoring, when low oil pressure (LOP), High temperate (HWT) and overspeed. Alternator switch, 3-pole with thermal and magnetic protection. Frequency meter, hours counter, voltmeter, ampere meter, optical and acoustic alarm. lectronic engine speed governor, AMF automatic control panel with ATS, for parallel operation with the mains supply or peak looping operation.
Tank
24h fuel tank, automatic fuel-fill-system.
Trailer
1 or 2 axle trailer.
Options
For all power generators is a wide range of accessories available.
Technical changes
We keep ahead.
We are pleased to answer your questions


    I have read and understood the privacy policy. I agree that my details and data will be collected and stored electronically for the purpose of responding to my enquiry. Please note: You can revoke your consent at any time by sending an email to info@wa-strom.com.