Iveco generators with 1,500 rpm at 50 Hz
61 to 400 kVA Iveco power generator
| Iveco generator type | kVA 100 % PRP* |
Iveco engine type |
| WA-I 60 | 61 | N 45 SM 1F |
| WA-I 85 | 85 | N 45 TE 1F |
| WA-I 100 | 103 | N 45 TE 2F |
| WA-I 135 | 132 | N 67 TM 1F |
| WA-I 160 | 154 | N 67 TE 1F |
| WA-I 200 | 200 | N 67 TE 3F |
| WA-I 250 | 250 | C 87 TE 3F |
| WA-I 350 | 350 | CE 13 TE 1F |
| WA-I 400 | 400 | C 13 TE 2F |
* Variable continuous power PRP (Prime Power): Maximum power for variable load, without time restriction per year. Average 24-hour operation should not exceed 80% of this power. For control purposes and starting heavy machinery, an overload of 10% for 1 hour within 12 hours is permissible. Operating mode according to ISO 8528. Maintenance must be observed here.
54,5 to 342,0 kW Iveco power generator
| Iveco generator type | Power KW |
Consumption 100 % load PRP |
| WA-I 60 | 54,5 KW | 16,70 L/h |
| WA-I 85 | 72,5 KW | 18,80 L/h |
| WA-I 100 | 89,0 KW | 22,60 L/h |
| WA-I 135 | 113,5 KW | 30,50 L/h |
| WA-I 160 | 131,5 KW | 34,00 L/h |
| WA-I 200 | 175,0 KW | 45,50 L/h |
| WA-I 250 | 232,0 KW | 59,00 L/h |
| WA-I 350 | 296,0 KW | 81,00 L/h |
| WA-I 400 | 342,0 KW | 92,90 L/h |
Iveco generators, model “G” on base frame
Version “G”: Stationary version (open design) on base frame
Tank capacity and length Iveco power generator
| Iveco generator type |
Tank capacity
in L |
Length
in mm
|
| WA-I 60 „G“ |
145
|
2.150
|
| WA-I 85 „G“ |
170
|
2.450
|
| WA-I 100 „G“ |
170
|
2.450
|
| WA-I 135 „G“ |
250
|
2.900
|
| WA-I 160 „G“ |
250
|
2.900
|
| WA-I 200 „G“ |
250
|
2.900
|
| WA-I 250 „G“ |
449
|
3.000
|
| WA-I 350 „G“ |
597
|
3.310
|
| WA-I 400 „G“ |
597
|
3.310
|
Width and height Iveco power generator
| Iveco generator type |
Width
in mm
|
Height
in mm
|
| WA-I 60 „G“ |
780
|
1.500
|
| WA-I 85 „G“ |
780
|
1.500
|
| WA-I 100 „G“ |
780
|
1.485
|
| WA-I 135 „G“ |
900
|
1.576
|
| WA-I 160 „G“ |
900
|
1.595
|
| WA-I 200 „G“ |
900
|
1.634
|
| WA-I 250 „G“ |
1.160
|
1.765
|
| WA-I 350 „G“ |
1.390
|
1.783
|
| WA-I 400 „G“ |
1.390
|
1.783
|
Weight Iveco power generator
| Iveco generator type |
Weight
in KG
|
| WA-I 60 „G“ |
948
|
| WA-I 85 „G“ |
1084
|
| WA-I 100 „G“ |
1.123
|
| WA-I 135 „G“ |
1.396
|
| WA-I 160 „G“ |
1.595
|
| WA-I 200 „G“ |
1.548
|
| WA-I 250 „G“ |
2.269
|
| WA-I 305 „G“ |
2.626
|
| WA-I 350 „G“ |
2.837
|
| WA-I 400 „G“ |
2.974
|
Iveco generators, model “S”, soundproofed
Version “S”: with weatherproof sound insulation hood
Tank capacity and db (A) Iveco power generator
| Iveco generator type |
Tank capacity
in L
|
db (A) *
7 Meter
|
| WA-I 60 „S“ |
240
|
69 |
| WA-I 85 „S“ |
240
|
69 |
| WA-I 100 „S“ |
240
|
68 |
| WA-I 135 „S“ |
450
|
68 |
| WA-I 160 „S“ |
450
|
68 |
| WA-I 200 „S“ |
450
|
68 |
| WA-I 250 „S“ |
449
|
70 |
| WA-I 305 „S“ |
597
|
68 |
| WA-I 350 „S“ |
597
|
68 |
| WA-I 400 „S“ |
597
|
68 |
* db(A) measured at 7 meters as the average value of an omnidirectional measurement at 7 measuring points
Length and width Iveco power generator
| Iveco generator type |
Lenght
in mm
|
Width
in mm
|
| WA-I 60 „S“ |
2.750
|
1.100
|
| WA-I 85 „S“ |
2.750
|
1.100
|
| WA-I 100 „S“ |
2.750
|
1.100
|
| WA-I 135 „S“ |
3.300
|
1.200
|
| WA-I 160 „S“ |
3.300
|
1.200
|
| WA-I 200 „S“ |
3.300
|
1.200
|
| WA-I 250 „S“ |
3.800
|
1.400
|
| WA-I 305 „S“ |
4.100
|
1.600
|
| WA-I 350 „S“ |
4.100
|
1.600
|
| WA-I 400 „S“ |
4.100
|
1.600
|
Height and weight Iveco power generator
| Iveco generator type |
Height
in mm
|
Weight
in KG
|
| WA-I 60 „S“ |
1.760
|
1.538
|
| WA-I 85 „S“ |
1.760
|
1.660 |
| WA-I 100 „S“ |
1.760
|
1.689 |
| WA-I 135 „S“ |
1.956
|
2.155 |
| WA-I 160 „S“ |
1.956
|
2.185 |
| WA-I 200 „S“ |
1.956
|
2.310 |
| WA-I 250 „S“ |
2.253
|
3.531 |
| WA-I 350 „S“ |
2.200
|
4.239 |
| WA-I 400 „S“ |
2.200
|
4.376 |
All data provided applies to the “Iveco generator” in the standard scope of delivery.