Iveco power generator
60 - 600 kVA Stage 2

on skid frame or silenced

Iveco generators with 1,500 rpm at 50 Hz

60 to 599 kVA Iveco power generator
Iveco generator type kVA 100 %
PRP*
Iveco engine type
WA-I 60 60 N 45 SM 1 A
WA-I 75 75 N 45 SM 2 A
WA-I 85 84 N 45 SM 3
WA-I 100 101 N 45 TM 2 A
WA-I 135 132 N 67 TM 2 A
WA-I 160 160 N 67 TM 3 A
WA-I 180 180 N 67 TE 2 A
WA-I 200 200 N 67 TE 2 A
WA-I 250 250 C 87 TE 1 D
WA-I 305 300 C 10 TE 1 D
WA-I 350 350 CE 13 TE 2 A
WA-I 400 400 C 13 TE 3 A
WA-I 500 500 C 13 TE 7
WA-I 600 599 CR 16 TE 1W

*Prime Power PRP. Maximum power for variable load, no time limit per year. The average 24 hours operation should not exceed 80% of that power. For control purposes an thrust harder Maschinery is an overload of 10% for 1 hour within 12 hours permitted. Mode according to ISO 8528. The maintenace is to be considered.

53,3 to 504,0 kW Iveco power generator
Iveco generator type Power
KW
Consumption
100 % load PRP
WA-I 60 53,3 KW 13,70 L/h
WA-I 75 66,1 KW 17,10 L/h
WA-I 85 73,3 KW 19,40 L/h
WA-I 100 87,5 KW 22,00 L/h
WA-I 135 114,2 KW 29,30 L/h
WA-I 160 137,7 KW 36,00 L/h
WA-I 180 175,0 KW 44,00 L/h
WA-I 200 175,0 KW 44,00 L/h
WA-I 250 232,2 KW 58,5 L/h
WA-I 305 264,0 KW 62,80 L/h
WA-I 350 300,0 KW 70,00 L/h
WA-I 400 352,0 KW 85,80 L/h
WA-I 500 425,0 KW 100,06 L/h
WA-I 600 504,0 KW 115,12 L/h

Iveco generators, model “G” on base frame

Version “G”: Stationary version (open design) on base frame

Tank capacity and length Iveco power generator
Iveco generator type
Tank capacity
in L
Length
in mm
WA-I 60 „G“
145
2.150
WA-I  75 „G“
145
2.150
WA-I 85 „G“
145
2.150
WA-I 100 „G“
145
2.150
WA-I 135 „G“
250
2.900
WA-I 160 „G“
250
2.900
WA-I 180 „G“
250
2.900
WA-I 200 „G“
250
2.900
WA-I 250 „G“
449
3.000
WA-I 305 „G“
597
3.310
WA-I 350 „G“
597
3.310
WA-I 400 „G“
597
3.310
WA-I 500 „G“
597
3.310
WA-I 600 „G“
740
3.600
Width and height Iveco power generator
Iveco generator type
Width
in mm
Height
in mm
WA-I 60 „G“
780
1.500
WA-I 75 „G“
780
1.500
WA-I 85 „G“
780
1.500
WA-I 100 „G“
780
1.500
WA-I 135 „G“
900
1.576
WA-I 160 „G“
900
1.576
WA-I 180 „G“
900
1.595
WA-I 200 „G“
900
1.634
WA-I 250 „G“
1.170
1.765
WA-I 305 „G“
1.390
1.777
WA-I 350 „G“
1.390
1.783
WA-I 400 „G“
1.390
1.783
WA-I 500 „G“
1.390
1.783
WA-I 600 „G“
1.460
1.990
Weight Iveco power generator
Iveco generator type
Weight
in KG
WA-I 60 „G“
948
WA-I 75 „G“
974
WA-I 85 „G“
978
WA-I 100 „G“
1.109
WA-I 135 „G“
1.412
WA-I 160 „G“
1.450
WA-I 180 „G“
1.493
WA-I 200 „G“
1.567
WA-I 250 „G“
2.439
WA-I 305 „G“
2.626
WA-I 350 „G“
2.789
WA-I 400 „G“
2.974
WA-I 500 „G“
3.305
WA-I 600 „G“
3.595

Iveco generators, model “S”, soundproofed

Version “S”: with weatherproof sound insulation hood

Tank capacity and db (A) Iveco power generator
Iveco generator type
Tank capacity
in L
db (A) *
 7 Meter
WA-I 60 „S“
240
69
WA-I 75 „S“
240
69
WA-I 85 „S“
240
69
WA-I 100 „S“
240
69
WA-I 135 „S“
450
68
WA-I 160 „S“
450
68
WA-I 180 „S“
450
68
WA-I 200 „S“
450
68
WA-I 250 „S“
449
68
WA-I 305 „S“
597
68
WA-I 350 „S“
597
68
WA-I 400 „S“
597
68
WA-I 500 „S“
597
80
WA-I 600 „S“
740
79

* db(A) measured at 7 meters as the average of all-round measurement at 7 measuring points.

Length and width Iveco power generator
Iveco generator type
Length
in mm
Width
in mm
WA-I 60 „S“
2.750
1.100
WA-I 75 „S“
2.750
1.100
WA-I 85 „S“
2.750
1.100
WA-I 100 „S“
2.750
1.100
WA-I 135 „S“
3.300
1.200
WA-I 160 „S“
3.300
1.200
WA-I 180 „S“
3.300
1.200
WA-I 200 „S“
3.300
1.200
WA-I 250 „S“
3.800
1.400
WA-I 305 „S“
4.100
1.600
WA-I 350 „S“
4.100
1.600
WA-I 400 „S“
4.100
1.600
WA-I 500 „S“
4.100
1.600
WA-I 600 „S“
4.500
1.800
Height and weight Iveco power generator
Iveco generator type
Height
in mm
Weight
in KG
WA-I 60 „S“
1.760
1.538
WA-I 75 „S“
1.760
1.564
WA-I 85 „S“
1.760
1.568
WA-I 100 „S“
1.760
1.689
WA-I 135 „S“
1.956
2.172
WA-I 160 „S“
1.956
2.210
WA-I 180 „S“
1.956
2.253
WA-I 200 „S“
1.956
2.327
WA-I 250 „S“
2.253
3.701
WA-I 305 „S“
2.200
4.028
WA-I 350 „S“
2.200
4.191
WA-I 400 „S“
2.200
4.376
WA-I 500 „S“
2.200
4.707
WA-I 600 „S“
2.340
5.305

 All data in basic model or series delivery.

We are pleased to answer your questions