MTU Emergency power systems
500 – 3.300 kVA

on skid frame or soundproofed

MTU generators with 1,500 rpm at 50 Hz

510 to 2.300 kVA MTU power generator
MTU generator type kVA
100 % PRP*
MTU engine type
WA-M 500
510 10 V 1600 G 20 F
WA-M 620
620 12 V 1600 G 10 F
WA-M 680
680 12 V 1600 G 20 F
WA-M 800
800 12 V 2000 G 26 F
WA-M 840
840 12 V 2000 G 26 F
WA-M 950
950 16 V 2000 G 16 F
WA-M 1050
1.050 16 V 2000 G 26 F
WA-M 1150
1.150 16 V 2000 G 36 F
WA-M 1250
1.250 18 V 2000 G 26 F
WA-M 1300 1.300 18 V 2000 G 26 F
WA-M 1400 1.400 12 V 4000 G 23 R
WA-M 1500 1.500 12 V 4000 G 23
WA-M 1650 1.650 12 V 4000 G 23
WA-M 1830 1.830 12 V 4000 G 63
WA-M 2000 2.000 16 V 4000 G 23
WA-M 2100 2.100 16 V 4000 G 23
WA-M 2300 2.300 16 V 4000 G 63

*Prime Power PRP. Maximum power for variable load, no time limit per year. The average 24 hours operation should not exceed 80% of that power. For control purposes an thrust harder Maschinery is an overload of 10% for 1 hour within 12 hours permitted. Mode according to ISO 8528. The maintenace is to be considered.

433 to 1.738 kW MTU power generator
MTU power generator Power
KW
Consumption
100 % load PRP
WA-M 500
433,0 KW 108 L/h
WA-M 620
506,0 KW 116 L/h
WA-M 680
558,0 KW 128 L/h
WA-M 800
675,0 KW 156 L/h
WA-M 840
 on demand  on demand
WA-M 950
762 KW 179 L/h
WA-M 1050
846 KW 197 L/h
WA-M 1150
956 KW 223 L/h
WA-M 1250
1.058 KW 242 L/h
WA-M 1300  on demand  on demand
WA-M 1400  on demand  on demand
WA-M 1500  on demand  on demand
WA-M 1650 1.370 KW 312 L/h
WA-M 1830 1.525 KW 353 L/h
WA-M 2000  on demand  on demand
WA-M 2100 1.738 KW 401 L/h
WA-M 2300  on demand  on demand

 

All specified data “MTU generator” included in standard delivery.

Basic equipment: MTU power generator

Power generator

The complete power generator is mounted on a steel base frame. On the steel base frame are specially designed devices, for lifting with a crane or Forklift. The diesel engine and the alternator are connected to a SAE-flange, that even a longer period of operation no possibility of an adjustment exists. The daily fuel tank is integrated in the steel base frame. The starter batteries of 12 or 24 volts are fixed on the steel base frame. Preheating-system 230 Volt DC.

Engine

MTU industrial diesel 4-stroke direct injection, watercooled 1.500 rpm (50 Hz). Low oil and fuel consumption with long maintenance intervals make a very economic engine application.

Alternator

Mecc Alte alternator, brushless self-exciting, self-regulating with electronic voltage regulator (AVR) according to VDE 0530, 400/230 volts, 4-pole, insulation class H.

Control Panel

Manual start-stop-system with engine shutdown during monitoring, when low oil pressure (LOP), High temperate (HWT) and overspeed. Alternator switch, 3-pole with thermal and magnetic protection. Frequency meter, hours counter, voltmeter, ampere meter, optical and acoustic alarm. Electronic engine speed governor, AMF automatic control panel with ATS, for parallel operation with the mains supply or peak looping operation.

Tank

24h fuel tank, automatic fuel-fill-system.

Trailer

1 or 2 axle trailer.

Options

For all power generators is a wide range of accessories available.

Technical changes

We keep ahead.

We are pleased to answer your questions


    I have read and understood the privacy policy. I agree that my details and data will be collected and stored electronically for the purpose of responding to my enquiry. Please note: You can revoke your consent at any time by sending an email to info@wa-strom.com.