Volvo power generators 250 – 760 kVA – 1.500 r.p.m diesel watercooled
85 to 760 kVA Volvo power generator
| Volvo generator type | kVA 100 % PRP* |
Engine type |
| WA-V 85 | 85 | TAD 530 GE |
| WA-V 100 | 100 | TAD 531 GE |
| WA-V 130 | 130 | TAD 532 GE |
| WA-V 150 | 150 | TAD 731 GE |
| WA-V 180 | 180 | TAD 732 GE |
| WA-V 200 | 200 | TAD 733 GE |
| WA-V 250 | 250 | TAD 734 GE |
| WA-V 300 | 300 | TAD 1341 GE |
| WA-V 350 | 350 | TAD 1342 GE |
| WA-V 380 | 380 | TAD 1343 GE |
| WA-V 400 | 450 | TAD 1344 GE |
| WA-V 450 | 454 | TAD 1345 GE |
| WA-V 500 | 508 | TAD 1641 GE |
| WA-V 600 | 595 | TAD 1642 GE |
| WA-V 610 | 610 | TWD 1643 GE |
| WA-V 640 | 640 | TWD 1643 GE |
| WA-V 660 | 660 | TWD 1644 GE |
| WA-V 700 | 700 | TWD 1645 GE |
| WA-V 760 | 760 | TWD 1744 GE |
*Prime Power PRP. Maximum power for variable load, no time limit per year. The average 24 hours operation should not exceed 80% of that power. For control purposes and start-up of heavy machinery an overload of 10% is permissible for 1 hour within 12 hours. Operating mode according to ISO 8528. The maintenace is to be considered.
74 to 645 kW Volvo power generator
| Volvo generator type | Power KWm. |
Consumption 100 % load PRP |
| WA-V 85 | 74 KW | 19,00 L/h |
| WA-V 100 | 88 KW | 23,00 L/h |
| WA-V 130 | 112 KW | 29,00 L/h |
| WA-V 150 | 133 KW | 34,00 L/h |
| WA-V 180 | 160 KW | 41,00 L/h |
| WA-V 200 | 177 KW | 46,00 L/h |
| WA-V 250 | 217 KW | 52,00 L/h |
| WA-V 300 | 275 KW | 68,00 L/h |
| WA-V 350 | 303 KW | 68,00 L/h |
| WA-V 380 | 325 KW | 82,00 L/h |
| WA-V 400 | 354 KW | 83,00 L/h |
| WA-V 450 | 388 KW | 92,00 L/h |
| WA-V 500 | 430 KW | 102,00 L/h |
| WA-V 600 | 503 KW | 117,00 L/h |
| WA-V 610 | 536 KW | 120,00 L/h |
| WA-V 640 | 536 KW | 120,00 L/h |
| WA-V 660 | 555 KW | 130,00 L/h |
| WA-V 700 | 595 KW | 139,00 L/h |
| WA-V 760 | 645 KW | 154,00 L/h |
Data sheets Volvo power generator
Volvo generators, model “G” on base frame
Version “G”: Stationary version (open design) on base frame
Tank capacity and length Volvo power generator
| Volvo generator type | Tank capacity in L |
Length in mm |
| WA-V 85 „G“ | 180 | 2.050 |
| WA-V 100 „G“ | 180 | 2.080 |
| WA-V 130 „G“ | 212 | 2.360 |
| WA-V 150 „G“ | 236 | 2.500 |
| WA-V 180 „G“ | 236 | 2.500 |
| WA-V 200 „G“ | 236 | 2.500 |
| WA-V 250 „G“ | 470 | 3.000 |
| WA-V 300 „G“ | 470 | 3.000 |
| WA-V 350 „G“ | 470 | 3.000 |
| WA-V 380 „G“ | 470 | 3.000 |
| WA-V 400 „G“ | 470 | 3.000 |
| WA-V 450 „G“ | 470 | 3.000 |
| WA-V 500 „G“ | 580 | 3.490 |
| WA-V 600 „G“ | 580 | 3.490 |
| WA-V 610 „G“ | 990 | 3.500 |
| WA-V 640 „G“ | 990 | 3.500 |
| WA-V 660 „G“ |
990 | 3.500 |
| WA-V 700 „G“ | 990 | 3.620 |
| WA-V 760 „G“ | 990 | 3.620 |
Width and height Volvo power generator
| Volvo generator type | Width in mm |
Height in mm |
| WA-V 85 „G“ | 930 | 1.713 |
| WA-V 100 „G“ | 930 | 1.719 |
| WA-V 130 „G“ | 1.035 | 1.763 |
| WA-V 150 „G“ | 1.035 | 1.737 |
| WA-V 180 „G“ | 1.035 | 1.737 |
| WA-V 200 „G“ | 1.035 | 1.737 |
| WA-V 250 „G“ | 1.200 | 1.834 |
| WA-V 300 „G“ | 1.200 | 2.160 |
| WA-V 350 „G“ | 1.200 | 2.163 |
| WA-V 380 „G“ | 1.200 | 2.141 |
| WA-V 400 „G“ | 1.200 | 2.141 |
| WA-V 450 „G“ | 1.200 | 2.111 |
| WA-V 500 „G“ | 1.300 | 2.226 |
| WA-V 600 „G“ | 1.300 | 2.219 |
| WA-V 610 „G“ | 1.330 | 2.400 |
| WA-V 640 „G“ | 1.330 | 2.400 |
| WA-V 660 „G“ | 1.330 | 2.816 |
| WA-V 700″G“ | 1.330 | 2.816 |
| WA-V 760″G“ | 1.330 | 2.816 |
Weight Volvo power generator
| Volvo generator type | Weight in KG |
| WA-V 85 „G“ | 1.240 |
| WA-V 100 „G“ | 1.300 |
| WA-V 130 „G“ | 1.480 |
| WA-V 150 „G“ | 1.580 |
| WA-V 180 „G“ | 1.850 |
| WA-V 200 „G“ | 1.820 |
| WA-V 250 „G“ | 2.050 |
| WA-V 300 „G“ | 2.800 |
| WA-V 350 „G“ | 2.850 |
| WA-V 380 „G“ | 2.940 |
| WA-V 400 „G“ | 2.940 |
| WA-V 450 „G“ | 3.180 |
| WA-V 500 „G“ | 3.620 |
| WA-V 600 „G“ | 3.680 |
| WA-V 610 „G“ | 4.330 |
| WA-V 640 „G“ | 4.350 |
| WA-V 660 „G“ | 4.500 |
| WA-V 700 „G“ | 4.750 |
| WA-V 760 „G“ | 4.850 |
“S” Silenced Volvo diesel gensets
Version “S”: with weatherproof sound insulation hood
Tank capacity and db (A) Volvo power generator
| Volvo generator type | Tank capacity in L |
db(A)* 7 Meter |
| WA-V 85 „S“ | 220 | 72 |
| WA-V 100 „S“ | 220 | 70 |
| WA-V 130 „S“ | 220 | 70 |
| WA-V 150 „S“ | 220 | 72 |
| WA-V 180 „S“ | 360 | 70 |
| WA-V 200 „S“ | 360 | 70 |
| WA-V 250 „S“ | 360 | 72 |
| WA-V 300 „S“ | 534 | 72 |
| WA-V 350 „S“ | 534 | 72 |
| WA-V 380 „S“ | 534 | 72 |
| WA-V 400 „S“ | 534 | 72 |
| WA-V 450 „S“ | 534 | 72 |
| WA-V 500 „S“ | 990 | 75 |
| WA-V 600 „S“ | 990 | 76 |
| WA-V 610 „S“ | 990 | 77 |
| WA-V 640 „S“ | 990 | 77 |
| WA-V 660 „S“ | 990 | 78 |
| WA-V 700 „S“ | 990 | 78 |
| WA-V 760 „S“ | 990 | 81 |
Length and width Volvo power generator
| Volvo generator type | Length in mm |
Width in mm |
| WA-V 85 „S“ | 2.950 | 1.100 |
| WA-V 100 „S“ | 2.950 | 1.100 |
| WA-V 130 „S“ | 2.950 | 1.100 |
| WA-V 150 „S“ | 2.950 | 1.100 |
| WA-V 180 „S“ | 3.600 | 1.350 |
| WA-V 200 „S“ | 3.600 | 1.350 |
| WA-V 250 „S“ | 3.600 | 1.350 |
| WA-V 300 „S“ | 4.200 | 1.600 |
| WA-V 350 „S“ | 4.200 | 1.600 |
| WA-V 380 „S“ | 4.200 | 1.600 |
| WA-V 400 „S“ | 4.200 | 1.600 |
| WA-V 450 „S“ | 4.200 | 1.600 |
| WA-V 500 „S“ | 4.860 | 2.060 |
| WA-V 600 „S“ | 4.860 | 2.060 |
| WA-V 610 „S“ | 4.860 | 2.060 |
| WA-V 640 „S“ | 4.860 | 2.060 |
| WA-V 660 „S“ | 4.860 | 2.060 |
| WA-V 700 „S“ | 4.860 | 2.060 |
| WA-V 760 „S“ | 4.860 | 2.060 |
Height and weight Volvo power generator
| Volvo generator type | Height in mm |
Weight in KG |
| WA-V 85 „S“ | 1.760 | 1.680 |
| WA-V 100 „S“ | 1.760 | 1.840 |
| WA-V 130 „S“ | 1.763 | 1.980 |
| WA-V 150 „S“ | 1.760 | 2.180 |
| WA-V 180 „S“ | 2.040 | 2.850 |
| WA-V 200 „S“ | 2.040 | 2.980 |
| WA-V 250 „S“ | 2.040 | 3.018 |
| WA-V 300 „S“ | 2.245 | 4.200 |
| WA-V 350 „S“ | 2.245 | 4.320 |
| WA-V 380 „S“ | 2.245 | 4.600 |
| WA-V 400 „S“ | 2.145 | 4.660 |
| WA-V 450 „S“ | 2.245 | 4.660 |
| WA-V 500 „S“ | 2.585 | 5.940 |
| WA-V 600 „S“ | 2.585 | 6.260 |
| WA-V 610 „S“ | 2.585 | 6.480 |
| WA-V 640 „S“ | 2.585 | 6.660 |
| WA-V 660 „S“ | 2.595 | 6.800 |
| WA-V 700 „S“ | 2.595 | 7.100 |
| WA-V 760 „S“ | 2.595 | 7.500 |
All specified data “Volvo generator” included in standard delivery.
High performance, maximum availability and fast installation
As Volvo Penta has over 100 years of industrial experience and therefore manufactures high-quality products, it is one of the world’s best-known diesel engine manufacturers. An emergency genset with a Volvo Penta engine is particularly resilient and can start quickly. Thanks to a low oil quantity, high quality and reliability as well as simple installation, the highly efficient engines ensure low operating costs. Maintenance intervals can be limited to up to 1000 hours. Volvo Penta engines are extremely economical and flexible. They meet all the requirements of G3 according to ISO8528-5.
Basic equipment Volvo power generators
Power generator
The complete generating set is mounted on a base frame made of welded steel edge profiles in a robust construction. Specially designed devices for lifting with a crane are attached to the base frame. The diesel engine and the generator are directly connected to each other via an SAE flange, so that there is no possibility of misalignment even after prolonged operation. The day tank is integrated in the base frame. The 12 / 24 volt DC starter batteries are mounted on the base frame and wired to the diesel engine.
Engine
Volvo industrial diesel engine 4-stroke direct injection, water-cooled 1,500 rpm (50 Hz). Low oil-fuel consumption with long maintenance intervals makes series a very economical engine application.
Generator
Mecc Alte, Stamford or Leroy Somer three-phase synchronous generator, brushless, self-regulating with electronic voltage regulator (AVR) to VDE 0100 Part 0530, 400/230 volts, 4-pole, insulation to Class H.
Switchgear
Manual start/stop system mounted on the generator set with engine monitoring and shutdown in the event of low oil pressure, overtemperature, overspeed, 3-pole generator switch with thermal and magnetic release. Optionally with fully automatic emergency power switchgear
Equipment
Frequency meter, operating hours counter, voltmeter and ammeter, visual and acoustic alarm display in the event of a malfunction of the generator set.
Documentation
Complete description, clearly filed for the engine, alternator and the entire system.
Work test
Every generator is tested in the test bay before leaving the factory.
Quality standards
WA Notstromtechnik GmbH backup power generators comply with the CE mark and the following additional regulations:
- 2006/42/ EC | CE & EN ISO 13857: 2008 Machine safety.
- ISO 8528-5: 2018-10 Power generating sets with reciprocating internal combustion engines Part 5
- 2014/30/EU Electromagnetic compatibility.
- 2006/95/EC Low Voltage Directive
- 2014/35/EU Electrical equipment designed for use within certain voltage limits
- 2000/14/CE Exposure of machinery to noise Outdoor use. (modified by 2005/88/CE)
- 2002/88/CE Exhaust emissions and particulate emissions. (modified by 2004/26/CE)
- AwSV Requirements for systems for handling substances hazardous to water & WHG (valid since 01.08.2017)
- EN 12100, EN 60204
Performance and installation conditions standardized according to DIN 6271 and ISO 3046: 1000 mbar, 25ºC, 30% relative humidity. If your application is part of a legally required safety power supply, for example for the operation of a sprinkler system, special requirements may be placed on the backup power unit and its peripherals. The team at WA Notstromtechnik GmbH will be happy to advise you on this and accompany your project through to final commissioning.
Optional at extra cost
backup power supplies are available in accordance with the following regulations:
- DIN VDE 0100 – 551 (2018-12) Installation of low-voltage systems, other equipment
- DIN VDE 0100 – 560 (2022-10) Installation of low-voltage systems, safety power sources
- DIN VDE 0100 – 710 (2012-10) Installation of low-voltage systems, areas used for medical purposes
- DIN VDE 0100 – 718 (2014-06) Requirements for premises and installations of a special kind, Public facilities
- DIN 6280 – 13 (1994-12) Safety power supply in hospitals and buildings for gatherings of people
- DIN EN ISO 8528 – 13 (2017-03) Generating sets with reciprocating internal combustion engines Part 13 Safety
- VdS CEA 4001 (2024-01) Requirements for generating sets for sprinkler systems
- DIN VDE AR – N 4105 (2018-1) Generating sets on the low-voltage grid
- 2016/1628 Exhaust gas emissions and pollutant particles (STAGE V)
Warranty
12 months or 2000 operating hours, whichever comes first, up to a maximum of 15 months after notification of readiness for dispatch. If maintenance is not carried out by a specialist company and the monthly test runs are not complied with, the guarantee/warranty claim expires.
Technical changes
We expressly reserve the right to make changes.